Plan Review Notes
Plan Review Notes For Permit 16120590
Permit Number 16120590
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-20 16:30:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE IS INSUFFICIENT INFORMATION CONTAINED IN THIS
 SUBMITTAL TO COMPLETE ANY KIND OF FORMAL REVIEW OF THE
 LIFE SAFETY SYSTEM PUMP REPLACEMENT OF THIS HEALTHCARE
 OCCUPANCY.
  
 THE FOLLOWING IS A BRIEF REVIEW OF THE LIMITED
 INFORMATION PROVIDED.
  
  
 THIS IS A LIFE SAFETY SYSTEM THAT FALLS UNDER THE SCOPE
 OF FS 61G AND SHALL FOLLOW THE REQUIREMENTS OF THE EOR.
  
 THIS PROPOSED REPLACEMENT BECOMES THE PUMP OF RECORD
 FOR THIS OCCUPANCY AND SHALL BE DOCUMENTED ON OFFICIAL
 PLAN SET DRAWINGS ON OFFICIAL TITLE BOLCK SETS OF THE
 INSTALLING CONTRACTOR.
  
 THE SUBMITTED INFORMATION, AT BEST, CAN BE ACCEPTED AS
 SUPPLEMENTAL INFORMATION OF THE PROPOSED INSTALLATION.
  
  
 1) ONLY ONE SET OF INFORMATION WAS SUBMITTED. A MINIMUM
 OF TWO SETS SHALL BE SUBMITTED. EACH SET SHALL INCLUDE
 AN OFFICIAL TITLE BLOCK, PUMP ROOM AND PUMP DRAWING
 LAYOUT OF ALL EQUIPMENT AND WATER DISTRIBUTION PIPING,
 INCLUDING A DEMO DRAWING AND THE LOCATION OF EXIT
 DOORS, THE MAIN PUMP, JOCKEY PUMP, CONTROLLER PANEL AND
 ANY OTHER EQUIPMENT WITHIN THE PUMP ROOM
  
 PLEASE PROVIDE AN ADDITIONAL SET WITH ALL THE
 APPLICABLE INFORMATION.
  
  
  
 2) THERE IS NO REFERENCE OF COMPLIANCE WITH ANY FIRE
 CODE. THE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE
 NFPA CODE, INCUDING BUT NOT LIMITED TO, NFPA 20,
 STANDARD FOR THE
 INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION
 2010 EDITION
  
 PLEASE PROVIDE AN APPLICABLE NOTE AND ENSURE COMPLIANCE
 IS MEET BY DESIGN AND INSTALLATION.
  
  
  
  
 3) THE EXISTING PUMP PICTURES INDICATED SOME UNREADABLE
 INFORMATION.
  
 PLEASE PROVIDE EXISTING AND PROPOSED INFORMATION IN A
 CLEAR AND READABLE FORMAT.
  
  
  
 4) THE IS NO DRAWING DETAIL OF THE EXISTING AND/OR
 PROPOSED PIPING LAYOUT, WATER DISTRIBUTION SYSTEM AND
 JOCKEY PUMP
  
 PER NFPA 20
  
 4.2* APPROVAL REQUIRED.
 4.2.1 STATIONARY PUMPS SHALL BE SELECTED BASED ON THE
 CONDITIONS UNDER WHICH THEY ARE TO BE INSTALLED AND
 USED.
  
 4.2.3 A COMPLETE PLAN AND DETAILED DATA DESCRIBING
 PUMP, DRIVER, CONTROLLER, POWER SUPPLY, FITTINGS,
 SUCTION AND DISCHARGE CONNECTIONS, AND LIQUID SUPPLY
 CONDITIONS SHALL BE PREPARED FOR APPROVAL.
  
 PLEASE PROVIDE THE APPLICABLE AND ACCURATE INFORMATION.
  
  
  
 5) THERE IS NO INDICATION OF PROVIDING FOR THE
 TEMPORARY SUPPORT OF THE SPRINKLER SYSTEM WHILE THE
 INSTALLATION IS UNDERWAY UNTIL COMPLETION AND TESTING.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY REVIEW OF THE
 INSTALLTION AND THE CONTINUE OPERATION AND MAINTENANCE
 OF THE CURRENT LIFE SAFETY SYSTEM.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved