Plan Review Notes For Permit 16120537 |
Permit Number |
16120537 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-22 10:16:47 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) SHEET T - THERE ISAN INCORRECT REFERENCE TO THE | | CURRENT EDITION OF THE FIRE CODE. | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | APPLICABLE CODES OR STANDARDS. | | | | PLEASE ENSURE COMPLIANCE AND UPDATE YOUR RECORDS FOR | | FUTURE SUBMITTALS. | | | | | | | | 2) SHEET A 7 - ANY AND ALL WORK ON THE FIRE ALARM | | SYSTEM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | PLEASE ENSURE COMPLIANCE | | | | | | | | 3) SHEET E 2.1 - THERE ARE 2 EXITS SIGNS INDICATED | | OUTSIDE A CORRIDOR THAT WOULD BE BETTER ERVED INSIDE | | THE CORRIDOR. | | | | PLEASE SEE THE HAND WRITTEN NOTE ON PLAN SHEET TO | | RELOCATE THEM. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|