Plan Review Notes
Plan Review Notes For Permit 16120506
Permit Number 16120506
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-17 04:17:071) THE GAS SIZING TABLE THAT HAS BEEN SUBMITTED NOTES
 THAT IT IS FOR A SUPPLY PRESSURE OF 11.0 INCHES W.C OR
 GREATER YET THE GAS RISER SHOWS THE SUPPLY PRESSURE
 GOING FROM 11INCHES W.C. TO 7 INCHES W.C. AND THEN TO
 11 INCHES W.C. CLARIFY.
 2) SUBMIT MANUF. SPECS FOR THE NEW RANGE. THE
 SPECIFICATIONS SHALL SHOW THAT THE RANGE IS LISTED AND
 LABELED PER 2014 FGC SEC.301.3.
 3) SUBMIT CALCULATIONS FOR COMBUSTION AIR.2014 FGC
 SEC.304.
 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE NEW
 RANGE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW