Plan Review Notes For Permit 16120447 |
Permit Number |
16120447 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-17 03:56:22 | 1) THIS PROJECT WAS NEVER REVIEWED FOR PLUMBING PLAN | | REVIEW (PERMIT #15110783). PROVIDE 2 COMPLETE SETS OF | | PLANS FOR REVIEW THAT ARE SIGNED AND SEALED BY THE | | DESIGN PROFESSIONAL OF RECORD.WPB AMEND. TO FBC SEC. | | 107.1, FAC RULE 61G15-23.001. | | 2) ONE OF THE PLUMBING DRAWINGS IS DONE IN PENCIL. | | DRAWINGS DONE IN PENCIL ARE NOT ACCEPTABLE.SUBMIT TWO | | COPIES OF THE SANITARY RISER THAT ARE NOT DONE IN | | PENCIL.WPB AMEND. TO FBC SEC. 107.1. | | 3) THE FLOOR DRAINS ARE NOT VENTED.2014 FPC SECS. | | 901.2, 901.2.1. | | 4) THE VENT SHALL CONNECT TO THE HORIZONTAL DRAIN IN | | ACCORDANCE WITH 2014 FPC SEC.905.3. | | 5) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS. 2014 FPC | | SEC.1002.4. | | 6) INDICATE ON THE FLOOR PLAN WHAT WILL BE DISCHARGING | | INTO THE FLOOR DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|