2016-12-17 03:56:221) THIS PROJECT WAS NEVER REVIEWED FOR PLUMBING PLAN
 REVIEW (PERMIT #15110783). PROVIDE 2 COMPLETE SETS OF
 PLANS FOR REVIEW THAT ARE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD.WPB AMEND. TO FBC SEC.
 107.1, FAC RULE 61G15-23.001.
 2) ONE OF THE PLUMBING DRAWINGS IS DONE IN PENCIL.
 DRAWINGS DONE IN PENCIL ARE NOT ACCEPTABLE.SUBMIT TWO
 COPIES OF THE SANITARY RISER THAT ARE NOT DONE IN
 PENCIL.WPB AMEND. TO FBC SEC. 107.1.
 3) THE FLOOR DRAINS ARE NOT VENTED.2014 FPC SECS.
 901.2, 901.2.1.
 4) THE VENT SHALL CONNECT TO THE HORIZONTAL DRAIN IN
 ACCORDANCE WITH 2014 FPC SEC.905.3.
 5) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS. 2014 FPC
 SEC.1002.4.
 6) INDICATE ON THE FLOOR PLAN WHAT WILL BE DISCHARGING
 INTO THE FLOOR DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
  