2016-12-15 11:49:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 10) BASED ON THE TRUSS DRAWINGS THE UPLIFT AND REACTION
 PRESSURES ARE SUBSTANTIALLY MORE AT THE TWO BEARING
 POINTS FOR THE NEW (3) MEMBER GIRDER THAN THE PREVIOUS
 DESIGN. THE ROOF TO WALL CONNECTIONS WILL NEED TO BE
 REVISED AT EACH END FOR THIS NEW GIRDER TRUSS. FBC-R
 802.1.7.5