2016-12-15 17:56:21CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL NOTES WITH REQUIRED INFORMATION
 ON SCOPE OF WORK,
 (2) PROVIDE CFM VALUE FOR EACH SUPPLY OUTLET.
 (3) PROVIDE EQUIPMENT SCHEDULE ON PLANS.
 (4) PROVIDE LOCATION OF CONDENSERS.
 (5) PROVIDE CONDENSER TIE DOWN DETAIL.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (6) PROVIDE AHRI
 (7) PROVIDE A BALANCED AIR FLOW THROUGH ALL SUPPLY
 OUTLETS AS PER THE TOTAL CFM DESIGN VALUES OF AHU #1 &
 #2.
  