Date |
Text |
2018-02-27 13:07:35 | FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESS. |
| |
| THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) THERE IS INSUFFICIENT DETAIL PROVIDING FOR THE |
| COMPLIANCE OF THE REQUIREMENTS OF ANY NFPA FIRE CODES. |
| |
| NFPA CODES AND/OR STANDARDS WILL BE WHAT FIRE |
| INSPECTIONS WILL BE BASED, PLEASE ENSURE COMPLAINCE. |
| |
| |
| |
| 2) PLEASE PROVIDE DETAILED INFOMATION AND NOTE |
| INDICATING COMPLIANCE WITH NFPA 780 - LIGHTNING |
| PROTECTION SYSTEMS. |
| |
| 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE |
| PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| PROVISIONS OF NFPA 780. |
| |
| |
| 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING |
| COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS |
| |
| INCLUDING, BUT NO LIMITED TO: |
| |
| CHAPTER 4 LOCATION OF WATER-COOLING TOWERS |
| 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS. |
| 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN, |
| DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT |
| ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE |
| MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE |
| REQUIRED. |
| 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE |
| COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE |
| IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE |
| WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN |
| ACCORDANCE WITH CHAPTER 4. |
| |
| 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE |
| CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT |
| SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND |
| METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT |
| AND NATURAL-DRAFT WATER-COOLING TOWERS: |
| (1) IMPORTANCE TO CONTINUITY OF OPERATION |
| (2)*SIZE AND CONSTRUCTION OF TOWER |
| (3) TYPE OF TOWER |
| (4) LOCATION OF TOWER |
| (5) WATER SUPPLY |
| (6) VALUE OF TOWER |
| (7) CLIMATE |
| (8)*WATER DELIVERY TIME |
| (9) ENVIRONMENT |
| (10) ROOFTOP TOWERS |
| (11) LIMITED ACCESS |
| (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1) |
| |
| 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS |
| WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK, |
| DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT |
| LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS: |
| (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING |
| BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS, |
| INCINERATORS, FLARE STACKS, OR COB BURNERS |
| (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH |
| AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES |
| MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT |
| PIPELINES AND PUMPING STATIONS |
| |
| 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS |
| WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED |
| WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH |
| 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100 |
| FT (30.5 M) FROM THE HAZARDS |
| LISTED IN SECTION 4.3. |
| |
| 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH |
| NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT |
| (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3. |
| |
| 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION. |
| TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE |
| PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED |
| IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE |
| LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS |
| LISTED IN SECTION 4.3. |
| |
| 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE |
| WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER |
| LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS |
| RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A |
| PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |