Plan Review Notes
Plan Review Notes For Permit 16120363
Permit Number 16120363
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2018-02-27 13:07:35FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESS.
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS INSUFFICIENT DETAIL PROVIDING FOR THE
 COMPLIANCE OF THE REQUIREMENTS OF ANY NFPA FIRE CODES.
  
 NFPA CODES AND/OR STANDARDS WILL BE WHAT FIRE
 INSPECTIONS WILL BE BASED, PLEASE ENSURE COMPLAINCE.
  
  
  
 2) PLEASE PROVIDE DETAILED INFOMATION AND NOTE
 INDICATING COMPLIANCE WITH NFPA 780 - LIGHTNING
 PROTECTION SYSTEMS.
  
 5.7* LIGHTNING PROTECTION. LIGHTNING PROTECTION, WHERE
 PROVIDED, SHALL BE INSTALLED IN ACCORDANCE WITH THE
 PROVISIONS OF NFPA 780.
  
  
 3) PLEASE PROVIDE DETAILED INFORMATION INDICATING
 COMPLIANCE WITH NFPA 214 - WATER-COOLING TOWERS
  
 INCLUDING, BUT NO LIMITED TO:
  
 CHAPTER 4 LOCATION OF WATER-COOLING TOWERS
 4.1 CONSTRUCTION MATERIALS OF WATER-COOLING TOWERS.
 4.1.1 WHERE THE COOLING TOWER'S STRUCTURE, FAN,
 DISTRIBUTION SYSTEM, LOUVERS, AND FILL AND DRIFT
 ELIMINATOR MATERIALS ARE ALL OF NONCOMBUSTIBLE
 MATERIALS, A FIRE PROTECTION SYSTEM SHALL NOT BE
 REQUIRED.
 4.1.2 IF ANY OF THE CONSTRUCTION MATERIALS ARE
 COMBUSTIBLE AND THE FACTORS IN SECTION 4.2 NECESSITATE
 IT, FIRE PROTECTION SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 5, AND TOWERS SHALL BE LOCATED IN
 ACCORDANCE WITH CHAPTER 4.
  
 4.2* FIRE RISK ANALYSIS. A FIRE RISK ANALYSIS SHALL BE
 CONDUCTED. THE FOLLOWING ARE SOME OF THE FACTORS THAT
 SHALL BE CONSIDERED IN DETERMINING THE EXTENT AND
 METHOD OF FIRE PROTECTION REQUIRED FOR INDUCED-DRAFT
 AND NATURAL-DRAFT WATER-COOLING TOWERS:
 (1) IMPORTANCE TO CONTINUITY OF OPERATION
 (2)*SIZE AND CONSTRUCTION OF TOWER
 (3) TYPE OF TOWER
 (4) LOCATION OF TOWER
 (5) WATER SUPPLY
 (6) VALUE OF TOWER
 (7) CLIMATE
 (8)*WATER DELIVERY TIME
 (9) ENVIRONMENT
 (10) ROOFTOP TOWERS
 (11) LIMITED ACCESS
 (12) MATERIALS OF CONSTRUCTION (SEE SECTION 4.1)
  
 4.3 COMBUSTIBLE EXTERIOR SURFACES. WATER-COOLING TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES, INCLUDING THE DECK,
 DISTRIBUTION BASINS, AND SO FORTH, SHALL BE LOCATED AT
 LEAST 100 FT (30.5 M) FROM THE FOLLOWING HAZARDS:
 (1) STRUCTURES OR PROCESSES THAT EMIT SPARKS OR FLYING
 BRANDS UNDER ORDINARY CIRCUMSTANCES, SUCH AS CHIMNEYS,
 INCINERATORS, FLARE STACKS, OR COB BURNERS
 (2) MATERIALS OR PROCESSES OF SEVERE FIRE HAZARD, SUCH
 AS PETROLEUM PROCESSING AND STORAGE TANKS, EXPLOSIVES
 MANUFACTURING OR STORAGE, AND PETROLEUM PRODUCT
 PIPELINES AND PUMPING STATIONS
  
 4.4 COMBUSTIBLE SURFACES WITH FIXED PROTECTION. TOWERS
 WITH COMBUSTIBLE EXTERIOR SURFACES THAT ARE PROVIDED
 WITH FIXED EXPOSURE PROTECTION IN ACCORDANCE WITH
 5.2.10 SHALL BE PERMITTED TO BE LOCATED CLOSER THAN 100
 FT (30.5 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.5 NONCOMBUSTIBLE EXTERIOR SURFACES. TOWERS WITH
 NONCOMBUSTIBLE EXTERIOR SURFACES SHALL BE LOCATED 40 FT
 (12 M) OR MORE FROM THE HAZARDS LISTED IN SECTION 4.3.
  
 4.6 NONCOMBUSTIBLE SURFACES WITH FIXED PROTECTION.
 TOWERS WITH NONCOMBUSTIBLE EXTERIOR SURFACES THAT ARE
 PROVIDED WITH FIXED INTERIOR FIRE PROTECTION INSTALLED
 IN ACCORDANCE WITH CHAPTER 5 SHALL BE PERMITTED TO BE
 LOCATED CLOSER THAN 40 FT (12 M) FROM THE HAZARDS
 LISTED IN SECTION 4.3.
  
 4.7 COMBUSTIBLE TOWERS ON BUILDING ROOFS. COMBUSTIBLE
 WATER-COOLING TOWERS LOCATED ON BUILDING ROOFS OR OTHER
 LOCATIONS TO WHICH ACCESS FOR MANUAL FIRE FIGHTING IS
 RESTRICTED OR DIFFICULT SHALL BE PROVIDED WITH A
 PROTECTION SYSTEM IN ACCORDANCE WITH CHAPTER 5.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  