2016-12-19 09:03:44 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16120363 | | 12/19/16 | | | | 1) SHEETS S-2 & M6.1: DIMENSIONS OF THE TOWER DON'T | | MATCH. | | | | 2) S-2: REFER TO TABLE 1509.6.5 FBC-14 BUILDING: | | MINIMUM 48 INCHES CLEARANCE DISTANCE REQUIRED BELOW THE | | NEW TOWER. | | | | 3) PROVIDE PIPING AND PIPE INSULATION SPECIFICATIONS. | | | | 4) PROVIDE DETAILS AND DTRAWINGS FOR THE ACCESS LADDER | | AND SERVICE PLATFORM- SEE SECTIONS 304.11, 306.1, & | | 306.5 | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TOWER. | | | | 6) COMMISSIONING OF THE SYSTEM IS REQUIRED IN | | ACCORDANCE WITH SECTION C408.2 FBC-14 ENERGY | | CONSERVATION. PLEASE SUBMIT A COMMISSIONING PLAN IN | | COMPLIANCE WITH SECTION C408.2.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|