Plan Review Notes For Permit 16120363 |
Permit Number |
16120363 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-29 13:53:19 | 16120363 | | 3800 WASHINGTON ROAD | | NEW COOLING TOWER | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | INDICATE SIZE OF EXISTING DISCONNECTS AND AND MOTOR | | CIRCUITS. VERIFY THE EXISTING CIRCUITS ARE ADEQUATE TO | | FEED THE NEW EQUIPMENT. PROVIDE A FEEDER DETAIL. NEC | | 215.5. 430.22 | | | | PROVIDE MOTOR OVERLOAD PROTECTION. NEC 430.32 | | | | PROVIDE MOTOR BRANCH CIRCUIT SHORT CIRCUIT AND GROUND | | FAULT PROTECTION. NEC 430.51 | | | | PROVIDE SAFE WORKING SPACE FOR DISCONNECTS. NEC 110.26 | | | | EQUIPMENT LIKELY TO BE SERVICE WHILE ENERGIZED MUST | | HAVE SAFETY WARNING LABELS TO PROTECT FROM ARC FLASH | | HAZARD. NEC 110.16 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-373-3701 | | [email protected] | | | | | | |
|