 3800 WASHINGTON ROAD
 NEW COOLING TOWER
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE SIZE OF EXISTING DISCONNECTS AND AND MOTOR
 CIRCUITS. VERIFY THE EXISTING CIRCUITS ARE ADEQUATE TO
 FEED THE NEW EQUIPMENT. PROVIDE A FEEDER DETAIL. NEC
 215.5. 430.22
  
 PROVIDE MOTOR OVERLOAD PROTECTION. NEC 430.32
  
 PROVIDE MOTOR BRANCH CIRCUIT SHORT CIRCUIT AND GROUND
 FAULT PROTECTION. NEC 430.51
  
 PROVIDE SAFE WORKING SPACE FOR DISCONNECTS. NEC 110.26
  
 EQUIPMENT LIKELY TO BE SERVICE WHILE ENERGIZED MUST
 HAVE SAFETY WARNING LABELS TO PROTECT FROM ARC FLASH
 HAZARD. NEC 110.16
  
  