Plan Review Notes
Plan Review Notes For Permit 16120363
Permit Number 16120363
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-15 07:18:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120363
 ADD: 3800 WASHINGTON RD.
 CONT: KCA CONSTRUCTION
 TEL: 561-361-0577
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 15/ 2016
 ACTION: DENIED
  
 1) ON THE PERMIT APPLICATION THE CONTRACTORS SIGNATURE
 IS A COPY, AN ORIGINAL SIGNATURE IS REQUIRED BEFORE
 PERMIT ISSUANCE. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 105.3.1 ACTION ON
 APPLICATION. IF THE APPLICATION OR THE CONSTRUCTION
 DOCUMENTS DO NOT CONFORM TO THE REQUIREMENTS OF
 PERTINENT LAWS, THE BUILDING OFFICIAL SHALL REJECT SUCH
 APPLICATION IN WRITING, STATING THE REASONS THEREFORE.
 IF THE BUILDING OFFICIAL IS SATISFIED THAT THE PROPOSED
 WORK CONFORMS TO THE REQUIREMENTS OF THIS CODE AND LAWS
 AND ORDINANCES APPLICABLE THERETO.
  
 2) SHEET S-1 MAKES REFERENCE TO CODE SECTION R4408.5.3.
 PLEASE CORRECT THIS CODE SECTION. THIS IS FOR SINGLE
 FAMILY RESIDENCES, STEEL IN THE HIGH-VELOCITY HURRICANE
 ZONES. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 4) SHEET S-2 INDICATES THE REPLACEMENT COOLING TOWER
 CT-1 TO BE A MARLEY 23121. PLEASE PROVIDE MANUFACTURERS
 PRODUCT INFORMATION THAT THIS MECHANICAL EQUIPMENT THAT
 IS EXPOSED TO WIND WAS DESIGNED TO RESIST WIND
 PRESSURES FOR THIS WIND SPEED AND ELEVATION. 2014 FBC-M
 301.15 WIND RESISTANCE.
  
 5) SHEET S1 AND S2 SHOW THE STEEL FRAMING SUPPORT
 STRUCTURE THE REPLACEMENT COOLING TOWER WILL REST UPON.
 THESE SHEETS SHOW BOTH WELDED AND BOLTED CONNECTIONS
 FROM STEEL FRAMING TO THE BUILDING STRUCTURE AND THE
 FRAMEWORK. WHAT THIS PLAN DOESN?T INDICATE IS THE
 CONNECTION FROM THE SUPPORT STEEL FRAMING TO THE
 COOLING TOWER.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  