2016-12-15 07:18:52 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16120363 |
| ADD: 3800 WASHINGTON RD. |
| CONT: KCA CONSTRUCTION |
| TEL: 561-361-0577 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. DEC. 15/ 2016 |
| ACTION: DENIED |
| |
| 1) ON THE PERMIT APPLICATION THE CONTRACTORS SIGNATURE |
| IS A COPY, AN ORIGINAL SIGNATURE IS REQUIRED BEFORE |
| PERMIT ISSUANCE. 2014 FLORIDA BUILDING CODE W 2014 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION 105.3.1 ACTION ON |
| APPLICATION. IF THE APPLICATION OR THE CONSTRUCTION |
| DOCUMENTS DO NOT CONFORM TO THE REQUIREMENTS OF |
| PERTINENT LAWS, THE BUILDING OFFICIAL SHALL REJECT SUCH |
| APPLICATION IN WRITING, STATING THE REASONS THEREFORE. |
| IF THE BUILDING OFFICIAL IS SATISFIED THAT THE PROPOSED |
| WORK CONFORMS TO THE REQUIREMENTS OF THIS CODE AND LAWS |
| AND ORDINANCES APPLICABLE THERETO. |
| |
| 2) SHEET S-1 MAKES REFERENCE TO CODE SECTION R4408.5.3. |
| PLEASE CORRECT THIS CODE SECTION. THIS IS FOR SINGLE |
| FAMILY RESIDENCES, STEEL IN THE HIGH-VELOCITY HURRICANE |
| ZONES. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS. |
| 2014 FBC-B 2204.1 WELDING |
| 201404.4.2 BOLTING. |
| |
| 4) SHEET S-2 INDICATES THE REPLACEMENT COOLING TOWER |
| CT-1 TO BE A MARLEY 23121. PLEASE PROVIDE MANUFACTURERS |
| PRODUCT INFORMATION THAT THIS MECHANICAL EQUIPMENT THAT |
| IS EXPOSED TO WIND WAS DESIGNED TO RESIST WIND |
| PRESSURES FOR THIS WIND SPEED AND ELEVATION. 2014 FBC-M |
| 301.15 WIND RESISTANCE. |
| |
| 5) SHEET S1 AND S2 SHOW THE STEEL FRAMING SUPPORT |
| STRUCTURE THE REPLACEMENT COOLING TOWER WILL REST UPON. |
| THESE SHEETS SHOW BOTH WELDED AND BOLTED CONNECTIONS |
| FROM STEEL FRAMING TO THE BUILDING STRUCTURE AND THE |
| FRAMEWORK. WHAT THIS PLAN DOESN?T INDICATE IS THE |
| CONNECTION FROM THE SUPPORT STEEL FRAMING TO THE |
| COOLING TOWER. |
| |
| LATERAL FORCE-RESISTING SYSTEM |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| THE PLAN REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW |
| COMMENTS FROM ALL DISCIPLINES: |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| US.ASPX. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |