Plan Review Notes
Plan Review Notes For Permit 16120344
Permit Number 16120344
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2016-12-27 07:44:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16120344
 ADD: 1301 SUMMIT BLVD. / PHASE 1 / EAST TICKET BOOTH
 CONT: GAST CONSTRUCTION
 TEL: 561-797-5907
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. DEC. 27/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN THE
 FLOOD ZONE TYPE A7 BASE FLOOD ELEVATION 12 FEET NGVD.
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. NOTE FOR PLAN REVIEW DOCUMENTS LINE C1OF THE
 FLOOD ZONE CERTIFICATE, THE CONSTRUCTION DRAW BOX
 SHOULD BE CHECKED!!!!!
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 2) SHEET E-1.1 SHOWS EXTERIOR YARD LIGHTING. SHEET A2.0
 DETAILS 2 & 3 BOTH SHOW NEW A/C COMPRESSOR PADS PLEASE
 PROVIDE THE PROPOSED HEIGHTS OF THESE ELEMENTS AND
 COMPLIANCE WITH THE FLOOD ZONE CERTIFICATE LINE C2 (E).
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE
 DESIGN FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY SHALL
 BE ESTABLISHED IN ACCORDANCE WITH SECTION 1612.3.1.
 2014 FBC-B 1612.3.1 DESIGN FLOOD ELEVATIONS.
  
 3) SHEET A2.0 DOES NOT PROVIDE WHAT THE FINISH FLOOR
 ELEVATIONS OF EITHER TICKET BOOTHS ARE? SHEET A5.0
 SHOWS AN EXTERIOR VIEW OF THE TICKET BOOTHS AND THE
 PROPOSED PATHWAY AT AN ELEVATION OF 0 FEET- 0 INCHES
 FINISH FLOOR ELEVATION. SHEET S-2.1 ALSO SHOWS A FINISH
 FLOOR ELEVATION OF 0 FEET. PLEASE PROVIDE THE FINISH
 FLOOR ELEVATION OF THE TICKET BOOTHS IN NGVD AND
 COMPLIANCE WITH 1612.3.1. 2014 FBC-B 1612.3.1 DESIGN
 FLOOD ELEVATIONS AND TTHE CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  