2016-12-28 13:56:20 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL |
| SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, SOLAR |
| PANELS, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, ETC. A |
| NOTE WILL SUFFICE. |
| 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| AND COMPLETIONS DOCUMENTS. |
| 3. PROVIDE A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| AND APPARATUSES ABOVE THE FLOOD PLAIN LEVEL. |
| 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING |
| REQUIREMENTS. |
| 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| VERBIAGE IN CODE. |
| 6. SOLAR SYSTEM SHOWN ON THESE DOCUMENTS WILL BE |
| SUBJECT TO A COMPLETE REVIEW UPON SEPARATE PERMIT |
| APPLICATION. NOTE THAT ALL NEC 690 REQUIREMENTS MUST BE |
| MET, EXAMPLE: GROUNDING SCHEME, BACK FED BREAKER SHOWN |
| ON LOAD CENTER P2, SIGNAGE ETC.? |
| 7. SHEET E2: LABEL ALL W/P RECEPTACLES TO BE GFCI |
| PROTECTED PER NEC 210.8B |
| 8. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL |
| DEPTH REQUIREMENTS FOR ALL U/G CONDUITS. |
| 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY |
| |
| |