Plan Review Notes
Plan Review Notes For Permit 16120344
Permit Number 16120344
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-28 13:56:20INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, SOLAR
 PANELS, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, ETC. A
 NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT
 AND APPARATUSES ABOVE THE FLOOD PLAIN LEVEL.
 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING
 REQUIREMENTS.
 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 6. SOLAR SYSTEM SHOWN ON THESE DOCUMENTS WILL BE
 SUBJECT TO A COMPLETE REVIEW UPON SEPARATE PERMIT
 APPLICATION. NOTE THAT ALL NEC 690 REQUIREMENTS MUST BE
 MET, EXAMPLE: GROUNDING SCHEME, BACK FED BREAKER SHOWN
 ON LOAD CENTER P2, SIGNAGE ETC.?
 7. SHEET E2: LABEL ALL W/P RECEPTACLES TO BE GFCI
 PROTECTED PER NEC 210.8B
 8. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL
 DEPTH REQUIREMENTS FOR ALL U/G CONDUITS.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  