2016-12-27 07:39:47 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16120344 |
| ADD: 1301 SUMMIT BLVD. / PHASE 1 / EAST TICKET BOOTH |
| CONT: GAST CONSTRUCTION |
| TEL: 561-797-5907 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 27/2016 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THIS PROPERTY IS LOCATED WITHIN THE |
| FLOOD ZONE TYPE A7 BASE FLOOD ELEVATION 12 FEET NGVD. |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION |
| IF PERMIT APPLICATION IS ON OR AFTER SEPT. 12/2016. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. NOTE FOR PLAN REVIEW DOCUMENTS LINE C1OF THE |
| FLOOD ZONE CERTIFICATE, THE CONSTRUCTION DRAW BOX |
| SHOULD BE CHECKED!!!!! |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| OMB NO. 1660-0008 |
| EXPIRATION DATE: NOV. 30/2018 |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 2) SHEET E-1.1 SHOWS EXTERIOR YARD LIGHTING. SHEET A2.0 |
| DETAILS 2 & 3 BOTH SHOW NEW A/C COMPRESSOR PADS PLEASE |
| PROVIDE THE PROPOSED HEIGHTS OF THESE ELEMENTS AND |
| COMPLIANCE WITH THE FLOOD ZONE CERTIFICATE LINE C2 (E). |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE |
| DESIGN FLOOD ELEVATIONS ARE NOT SPECIFIED, THEY SHALL |
| BE ESTABLISHED IN ACCORDANCE WITH SECTION 1612.3.1. |
| 2014 FBC-B 1612.3.1 DESIGN FLOOD ELEVATIONS. |
| |
| 3) SHEET A2.0 DOES NOT PROVIDE WHAT THE FINISH FLOOR |
| ELEVATIONS OF EITHER TICKET BOOTHS ARE? SHEET A5.0 |
| SHOWS AN EXTERIOR VIEW OF THE TICKET BOOTHS AND THE |
| PROPOSED PATHWAY AT AN ELEVATION OF 0 FEET- 0 INCHES |
| FINISH FLOOR ELEVATION. SHEET S-2.1 ALSO SHOWS A FINISH |
| FLOOR ELEVATION OF 0 FEET. PLEASE PROVIDE THE FINISH |
| FLOOR ELEVATION OF THE TICKET BOOTHS IN NGVD AND |
| COMPLIANCE WITH 1612.3.1. 2014 FBC-B 1612.3.1 DESIGN |
| FLOOD ELEVATIONS AND TTHE CITY OF WPB CODE OF |
| ORDINANCES SECTION 94-546. |
| |
| 4) KAWNEER PRODUCT APPROVALS FOR 350/500 -IR OUTSWING |
| DOORS AND KAWNEER PRODUCT APPROVAL REPORT FOR 8400 |
| LARGE MISSILE IMPACT SLIDING GLASS WINDOWS BOTH NEED TO |
| APPLY FOR A LOCAL PRODUCT APPROVAL COMPLETING THE CITY |
| OF WEST PALM BEACH LOCAL PRODUCT APPROVAL FORMS AND BE |
| RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW BY THE |
| W. P. B. BUILDING OFFICIAL. |
| |
| FORMS SENT TO JEFF/ [email protected] |
| 12/27/2016 08:02 AM. , |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |