2017-01-10 19:00:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT HEATING AND COOLING EQUIPMENT SIZING
 CALCULATIONS. FBCR-M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT AND APPLIANCES SHALL BE SIZED IN ACCORDANCE
 WITH ACCA MANUAL S BASED ON BUILDING LOADS CALCULATED
 IN ACCORDANCE WITH ACCA MANUAL J OR OTHER APPROVED
 HEATING AND COOLING CALCULATION METHODOLOGIES.
  
  