2017-01-11 09:35:03 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | FUEL GAS REVIEW DENIED | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE APPEARS TO BE A TYPO FOR THE REFERENCED | | FLORIDA GAS CODE EDITION 1010. THE 2014 FBC FUEL GAS IS | | THE APPLICABLE CODE. | | | | 2) THE TABLE THAT IS SPECIFIED 402.4(13) IS FOR | | SEMI-RIDGED COPPER TUBING. THE CORRECT ONE FOR CSST IS | | TABLE 402.4(15). | | | | 3) THE PRESSURE DROP SHOULD BE 0.5 INCH WATER COLUMN | | AND NOT 05. IN. W.C. PER TABLE 402.4(15). | | | | 4) SINCE THE LENGTH OF PIPING FOR EACH SECTION OF | | PIPING WAS NOT PROVIDED, YOU ARE APPARENTLY USING THE | | LONGEST LENGTH METHOD FOR PIPE SIZING. USING THE 150 | | FT. LENGTH FROM THE TABLE THE EHD 30 IS GOOD FOR 78,000 | | BTUS AND THE RANGE REQUIRES 80,000 BTUS. THE EHD 37 IS | | GOOD FOR 171,000 BTUS AND THE TANKLESS WATER HEATER | | REQUIRES 199,000 BTUS. PLEASE CORRECT. FBC FUEL GAS | | SECTION 402.4.1 | | | | |
|