Plan Review Notes
Plan Review Notes For Permit 16120276
Permit Number 16120276
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-12 17:05:04 
  
  
 SUBMIT FOR SEPARATE PERMIT FOR EACH SYSTEM.
 SHOW EACH SYSTEMS GENERAL LOCATION(ROOM/AREA), INCLUDE
 A BASIC LAYOUT OF THE BUILDING AS A REFERENCE.
 INCLUDE WHAT TYPE OF AGENT WILL BE USED IN EACH SYSTEM.
 PROVIDE DOCUMENTATION OF CHEMICAL USED IN DIP TANK AND
 COMPATABILITY OF EXTINGUISHING AGENT FROM THE
 MANUFACTURE.
 DIP TANK SHALL BE PROTECTED IN ACCORDANCE WITH NFPA 1,
 NFPA 33, AND NFPA 34.
 R. LINDOW 12-12-16