Plan Review Notes
Plan Review Notes For Permit 16120270
Permit Number 16120270
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-04 12:17:492ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120270
 12/28/16
  
 1) PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILLS AT
 THE MECHANICAL ROOM- 601.5
  
 2) SHOW THE LOCATION(S) OF THE REQUIRED SMOKE
 DETECTOR(S) IN THE MECHANICAL ROOM- SECTION 606.2.2
  
 3) SHOW THE LOCATION OF THE O/A DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved