2016-12-14 10:46:31JOB PERMIT NUMBER: 16120196
 JOB ADDRESS: 1911 N FLAGLER DRIVE
 WEST PALM BEACH FLORIDA 33407
 DATE: DECEMBER 14, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] SHOW EXITS SIGNS ON THE ELECTRICAL LIGHTING PLAN.
 FBC-1011.
  
 2] PROVIDE AN OCCUPANCY SENSOR IN OFFICE SUITE 102.
 FBC-E SECTION C405.2.2.2.
  
 3] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT
 FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW
 SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM
 PROVISIONS ASTM 635C & 636C.
  
 4] PROVIDE PULL BOX SIZE TO MEET MINIMUM REQUIREMENTS
 OF NEC 314.28.
  
 5] ADD A NOTE FOR SOURCE OF SUPPLY MARKING ON PANEL "B"
 PER NEC 408.4(B).
  
 6] ADD A NOTE THAT LOW VOLTAGE SHALL BE UNDER A
 SEPARATE PERMIT.
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER