2017-02-24 12:19:083RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 2/24/17
  
 1) PLEASE REMOVE THE FIRE SUPPRESSION PLANS AND THE M-1
 PLAN FROM THE PLAN SETS. THIS PERMIT APPLICATION IS
 SOLEY FOR THE KITCHEN EXHAUST HOOD. A SEPARATE PERMIT
 IS REQUIRED FOR THE FIRE SUPPRESSION SYSTEM, AND THE
 REVISED M-1 PLAN SHEET MUST BE SUBMITTED AS A REVISION
 OT MASTER PERMIT #16040451.
  
 2) THE SUBMITTED KITCHEN EXHAUST PLANS APPEAR TO COPIES
 FROM AN ORIGINAL SET AND MUCH OF THE PRINT IS
 ILLEGIBLE. I HAVE SPOKEN WITH LORI FROM HOOD DEPOT AND
 THEY ARE READY TO RESUBMIT CLEAR, CORRECTED, SIGNED AND
 SEALED PLANS ADDRESSING THE PREVIOUS REVIEW COMMENT ON
 1/03/2017.
  