2017-01-03 09:41:042ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 1/3/17
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. PLEASE
 PROVIDE AN AC LOAD CALCULATION THAT INCLUDES THE
 ADDITIONAL HEAT GAIN FROM THE MAKEUP AIR, AND THAT
 INDICATES THE ADDITIONAL LOAD DOES NOT EXCEED THE
 CAPACITY OF THE EXISTING OR PROPOSED AC SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719