Plan Review Notes For Permit 16120133 |
Permit Number |
16120133 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-27 12:25:02 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16120133 | | 12/27/16 | | | | 1) THE 1" CLEARANCE FOR THE HOOD TO THE COMBUSTIBLE | | CEILING AND WALLS IS NOT PERMITTED PER TABLE 308.6 | | FBC-14 MECHANICAL, AND NFPA-96 SECTION 4.2.3.2, TABLE | | A.3.3.37, AND FIGURE A.4.2(H). PLEASE CORRECT THE | | PLANS. | | | | 2) INDICATE COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR | | TEMPERATURE. | | | | 3) IT APPEARS THAT GURADS WILL BE REQUIRED AT THE ROOF | | EDGE THAT IS SHOWN IN CLOSE PROXIMITY TO THE EXHAUST | | FAN ON SHEET 4- SEE SECTION 304.11. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|