Plan Review Notes
Plan Review Notes For Permit 16120133
Permit Number 16120133
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-27 12:25:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120133
 12/27/16
  
 1) THE 1" CLEARANCE FOR THE HOOD TO THE COMBUSTIBLE
 CEILING AND WALLS IS NOT PERMITTED PER TABLE 308.6
 FBC-14 MECHANICAL, AND NFPA-96 SECTION 4.2.3.2, TABLE
 A.3.3.37, AND FIGURE A.4.2(H). PLEASE CORRECT THE
 PLANS.
  
 2) INDICATE COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE.
  
 3) IT APPEARS THAT GURADS WILL BE REQUIRED AT THE ROOF
 EDGE THAT IS SHOWN IN CLOSE PROXIMITY TO THE EXHAUST
 FAN ON SHEET 4- SEE SECTION 304.11.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER