2017-01-24 13:26:15 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16120124 |
| ADD: 723 39TH ST. |
| CONT: WEST CONSTRUCTION INC./ MARTHA A. MORGAN |
| TEL: 561-248-3868 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JAN. 24, 2017 |
| ACTION: DENIED |
| |
| 1) CONTRACTOR (QUALIFIER) NEEDS TO SIGN THE PERMIT |
| APPLICATION UNDER THE HEADING SIGNATURE OF CONTRACTOR |
| |
| 2) THE ADDRESS PROVIDED ON THE APPLICATION 723 39TH ST. |
| APPEARS TO BE AN OFFICE BUILDING, PERHAPS THE |
| ADMINISTRATIVE OFFICES FOR THE BOYS & GIRLS CLUB |
| ATHLETIC CENTER ADDRESSED AS 4017 PINEWOOD AVE. THE |
| ORIGINAL BOYS & GIRLS CLUB ATHLETIC CENTER PERMIT |
| 03060499 HAD A FEW PLANS INDICATING THE LOCATION OF THE |
| NORTHWOOD CENTER SPLASH PAD, SHEET C-3. THE ACTUAL |
| PERMIT FOR THE NORTHWOOD CENTER SPLASH PAD PERMIT |
| 03060502 WAS NEVER ISSUED AND VOIDED. THE PLAN |
| DOCUMENTS WERE ADDRESSED UNDER 4105 PINEWOOD AVE. THE |
| FOUNTAIN PLAZA IS NOT ON ANY PRIVATE PROPERTY BUT IN |
| THE RIGHT OF WAY. PLEASE UPDATE THE ADDRESS TO ONE THAT |
| IS ADJACENT TO THE RIGHT OF WAY WHERE THE PROJECT IS |
| LOCATED. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED UNDER THIS PERMIT. |
| |
| 3) THE DOCUMENTS SUBMITTED F1OF 4 WERE CREATED |
| ORIGINALLY BY JOHN BROWN P. E. 30698 DATED 09/06/05. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| |
| FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| 05/06/2009. (2)(A) EVERY SHEET OF PLANS AND PRINTS |
| WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER |
| 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE |
| PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| |
| 4) THE SUBMITTED PLANS F1 OF 4 HAVE BEEN REDUCED IN |
| SIZE AND NOT TO THE MINIMUM 1/8 INCH SCALE. PLANS ARE |
| SO SMALL THEY ARE ILLEGIBLE. 107.2.1.4 QUALITY OF |
| BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR |
| OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. |
| |
| 5) THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK |
| TO BE MAINTENANCE AND REHABILITATION. PLEASE DOCUMENT |
| WHAT WORK IS GOING TO OCCUR UNDER THIS PERMIT. SHEET F2 |
| OF 4 HAS A LEGEND FOR RETURN PIPES AND SUPPLY PIPES. |
| ARE PIPES TO BE REPLACED, IS CONCRETE DECK TO BE |
| REMOVED AND OR PAVERS? THERE ARE NO SHEETS INDICATING |
| THERE IS TO BE ANY STRUCTURAL WORK OCCURRING UNDER THIS |
| PERMIT? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 6) ONE SINGLE SHEET WITH GENERAL NOTES. THERE IS NO |
| TITLE BLOCK ON THIS SHEET, NO ONE HAS TAKEN |
| RESPONSIBILITY OF OWNERSHIP FOR THIS DOCUMENT. 107.3.4 |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |