2016-12-12 06:57:561) SHOW THE DISTANCE FROM THE RELIEF VALVE ON THE LP
 TANK TO THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH
 NFPA 58 SEC.6.3.4.2.
 2) SHOW THE DISTANCE OF THE LP TANK FROM THE PROPERTY
 LINE.COMPLY WITH NFPA 58 TABLE 6.3.1.
 3) YOU HAVE SUBMITTED TWO DIFFERENT SIZING TABLES WITH
 THIS PERMIT - ONE FOR A 10 PSI SYSTEM WITH DRISCOPLEX
 PIPE AND ONE FOR A 11.0 INCH W.C.( LOW PRESSURE) SYSTEM
 WITH SCH. 40 METALLIC PIPE BUT NO METALLIC PIPE IS
 SHOWN.CLARIFY. SHOW WHAT THE PSI OF THE SYSTEM IS ON
 THE PE PIPE.
 4) SHOW THE LOCATION OF THE U/G GAS LINE FROM THE TANK
 TO ITS TERMINATION POINT ABOVE GROUND ON THE SURVEY.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW