Plan Review Notes
Plan Review Notes For Permit 16120083
Permit Number 16120083
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-06 10:18:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN SHEET TITLE BLOCK AND CALCULATION TABLES
 INDICATES"MILLER RESIDENCE". THIS OCCUPANCY IS NO
 LONGER "MILLER RESIDENCE". IT IS "CASTLE RESEDENTIAL
 SERVICES"
  
 PLEASE UPDATE ALL REFERENCES OF THE PREVIOUS OCCUPANCY
 TO THE NEW OCCUPANCY.
  
  
 2) THERE IS NO INDICATIONS OF WHERE ANY NEW PIPE OF
 SPRINKLERS HAVE BEEN ADDED.
  
 PLEASE PROVIDE CLOUDED REVISIONS TO ALL NEW PIPE AND
 HEADS.
  
 NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  