Plan Review Notes
Plan Review Notes For Permit 16120061
Permit Number 16120061
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-20 14:35:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE 6 FT HIGH FENCE SHOWN IN DETAIL 4 ON AS-1,
 SPECIFIES A 4 X 4 X 6' PT. POST. THE POSTS FOR THE 6 FT
 FENCE WILL HAVE TO BE 8 FT IN ORDER TO HAVE 2 FT IN THE
 GROUND. PLEASE CORRECT. FBC 107.2.1
  
 2) THERE IS A NOTE THAT SPECIFIES HARDIPLANK SIDING ON
 THE GABLE END ON WALL SECTION 2 ON S1.1. THE REST OF
 THE PLANS INDICATE THAT THE GABLE WILL BE STUCCO WITH
 SIMULATED 6" HORIZONTAL LAPS. PLEASE CLARIFY. FBC
 107.2.1 NOTE: IF HARDI PLANK IS USED, SUBMIT TWO SETS
 OF PRODUCT APPROVALS FOR IT PER FBC 107.3.4.1.
  
 3) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 -
 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY
 CONSERVATION RESIDENTIAL PROVISIONS
 A) THERE WERE TWO ENERGY FORMS SUBMITTED WITH DIFFERNT
 INFORMATION. THE NUMBER OF OCCUPANTS AND THE ATTIC VENT
 RATIO ARE DIFFERENT. PLEASE CLARIFY AND REMOVE THE ONE
 THAT IS NOT SPECIFIC TO THIS PROJECT. FBC 107.2.1
 B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM
 PER FBC ENERGY CONSERVATION SECTION R103.1.1.2.
 C) THE FORM LISTS A 50 GAL. WATER HEATER AND A 40 GAL.
 WATER HEATER IS SPECIFIED ON PLAN SHEET P-1.0.
 D) THE FORM SPECIFIES A HIP ROOF AND THE PLANS SHOW A
 GABLE ROOF.
 E) THE PERMIT OFFICE IS WEST PALM BEACH AND THE
 JURISDICTION IS 604700. THESE WERE LEFT BLANK ON THE
 FORM.
  
 4) THE PLANS SPECIFY LOMANCO 700 SERIES LOUVERED STATIC
 ROOF VENTS. THE PRODUCT APPROVAL NUMBER ON THE PLANS
 AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR
 LOMANCO WHIRLYBIRD WIND TURBINES (NOA NO. 15-0831.08).
 THE PRODUCT APPROVAL FOR THE LOMANCO 700 SERIES VENTS
 IS NOA NO. 16-0510.28. NOTE: IF YOU USE THE WIND
 TURBINES PLEASE BE ADVISED THAT THE TAS 110 (A)
 STANDARD TO WHICH THEY WERE TESTED REQUIRES THAT THE
 TURBINE UNIT BE REMOVED AND REPLACED WITH A STORM CAP
 WHEN TESTING FOR WINDSPEED AND WATER SPRAY ABOVE A 70
 MPH WINDSPEED. FBC TEST PROTOCALS FOR HIGH VELOCITY
 HURRICANE ZONES (TAS) NO. 100(A)-95
  
 5) THE VALUATION HAS BEEN ADJUSTED FROM $130,000.00 TO
 $146,586.71 BASED ON CURRENT ICC VALUATION DATA. FBC
 109.3.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  