2017-01-20 14:35:22 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE 6 FT HIGH FENCE SHOWN IN DETAIL 4 ON AS-1, |
| SPECIFIES A 4 X 4 X 6' PT. POST. THE POSTS FOR THE 6 FT |
| FENCE WILL HAVE TO BE 8 FT IN ORDER TO HAVE 2 FT IN THE |
| GROUND. PLEASE CORRECT. FBC 107.2.1 |
| |
| 2) THERE IS A NOTE THAT SPECIFIES HARDIPLANK SIDING ON |
| THE GABLE END ON WALL SECTION 2 ON S1.1. THE REST OF |
| THE PLANS INDICATE THAT THE GABLE WILL BE STUCCO WITH |
| SIMULATED 6" HORIZONTAL LAPS. PLEASE CLARIFY. FBC |
| 107.2.1 NOTE: IF HARDI PLANK IS USED, SUBMIT TWO SETS |
| OF PRODUCT APPROVALS FOR IT PER FBC 107.3.4.1. |
| |
| 3) THERE ARE SOME ISSUES WITH THE ENERGY FORMS R405 - |
| 2014 THAT WERE SUBMITTED. PLEASE CORRECT. FBC ENERGY |
| CONSERVATION RESIDENTIAL PROVISIONS |
| A) THERE WERE TWO ENERGY FORMS SUBMITTED WITH DIFFERNT |
| INFORMATION. THE NUMBER OF OCCUPANTS AND THE ATTIC VENT |
| RATIO ARE DIFFERENT. PLEASE CLARIFY AND REMOVE THE ONE |
| THAT IS NOT SPECIFIC TO THIS PROJECT. FBC 107.2.1 |
| B) THE OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE FORM |
| PER FBC ENERGY CONSERVATION SECTION R103.1.1.2. |
| C) THE FORM LISTS A 50 GAL. WATER HEATER AND A 40 GAL. |
| WATER HEATER IS SPECIFIED ON PLAN SHEET P-1.0. |
| D) THE FORM SPECIFIES A HIP ROOF AND THE PLANS SHOW A |
| GABLE ROOF. |
| E) THE PERMIT OFFICE IS WEST PALM BEACH AND THE |
| JURISDICTION IS 604700. THESE WERE LEFT BLANK ON THE |
| FORM. |
| |
| 4) THE PLANS SPECIFY LOMANCO 700 SERIES LOUVERED STATIC |
| ROOF VENTS. THE PRODUCT APPROVAL NUMBER ON THE PLANS |
| AND THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE FOR |
| LOMANCO WHIRLYBIRD WIND TURBINES (NOA NO. 15-0831.08). |
| THE PRODUCT APPROVAL FOR THE LOMANCO 700 SERIES VENTS |
| IS NOA NO. 16-0510.28. NOTE: IF YOU USE THE WIND |
| TURBINES PLEASE BE ADVISED THAT THE TAS 110 (A) |
| STANDARD TO WHICH THEY WERE TESTED REQUIRES THAT THE |
| TURBINE UNIT BE REMOVED AND REPLACED WITH A STORM CAP |
| WHEN TESTING FOR WINDSPEED AND WATER SPRAY ABOVE A 70 |
| MPH WINDSPEED. FBC TEST PROTOCALS FOR HIGH VELOCITY |
| HURRICANE ZONES (TAS) NO. 100(A)-95 |
| |
| 5) THE VALUATION HAS BEEN ADJUSTED FROM $130,000.00 TO |
| $146,586.71 BASED ON CURRENT ICC VALUATION DATA. FBC |
| 109.3. |
| |
| 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |