Plan Review Notes
Plan Review Notes For Permit 16120004
Permit Number 16120004
Review Stop P
Sequence Number 1
Notes
Date Text
2016-12-14 17:50:281ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P 2.6 AND P2.6 YOUR NOTE FOR THE ROOF RAIN
 WATER CALCULATIONS DOES NOT MATCH THE TABLE IN THE FBC
 PL TABLE 1106.3 SIZE OF HORIZONTAL STORM DRAINGE PIPING
 A) THE RAIN FALL RATE IS 5" NOT 4.5".
 B) THE PIPE SIZE 4.5" DOES-NOT EXIST.
 C) THE SQ FT ON EACH PIPE DOES NOT MATCH THE TABLE.
 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE THE SLOPE OF THE PIPE ON THE RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
 IF THE HORIZONTAL 12" PIPE IS RUN AT 1/8 PER FT IT IS
 UNDER SIZED. PER FBC PL TABLE 1106.3
  