Notes |
Date |
Text |
2016-12-03 03:51:28 | 1) SUBMIT FACTORY SIZING CALCULATIONS FOR THE | | INTERCEPTORS FROM SCHIER TO ENSURE PROPER SIZING HAS | | BEEN DONE. FBC-PLUMBING, SEC. 1003.2. | | 2) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE NEW | | TANKS. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) A SAMPLING PORT SHALL BE INSTALLED ON THE DISCHARGE | | LINE FROM THE INTERCEPTOR. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|