2016-12-30 17:29:33 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY MECHANICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THERE IS NO RETURN SHOWN ON THE PLANS FOR BEDROOM #1 |
| ON THE FIRST FLOOR. M1602.4 BALANCED RETURN AIR. |
| RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS |
| ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS |
| IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING |
| SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS |
| RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN |
| PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH |
| RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID |
| UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED |
| BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS |
| CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL |
| BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS. |
| PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING |
| SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5 |
| PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER |
| PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE. |
| |
| 2) REVISE THE EQUIPMENT SIZING CALCULATIONS FOR UNIT 2, |
| USING THE EAST WALL WITH OPENINGS INSTEAD OF THE WEST |
| WALL. FBC ENERGY CONSERVATION SECTION 405 |
| |
| 3) THE PLANS NEED TO SPECIFY THAT THE DOORS TO THE |
| AIRHANDLER CLOSET ARE REQUIRED TO BE LOUVERED FOR |
| RETURN AIR. FBC 107.2.1 |
| |
| 4) THE 10 " DIAMETER RETURN AIR TRANSFER DUCT SERVING |
| THE MASTER BEDROOM IS NOT ADEQUATE FOR ALL OF THE |
| SUPPLY AIR IN THE MASTER BEDROOM. IT APPEARS THAT A 14" |
| DIAMETER WOULD BE REQUIRED. M1602.4 BALANCED RETURN |
| AIR. EXCEPTIONS: |
| |
| 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER |
| RETURN AIR BALANCE. |
| |
| 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (32 258 |
| MM2) (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR |
| SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING AN |
| UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| |
| 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE |
| REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, |
| EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| BE INCLUDED. |
| |
| |
| |
| |
| |