2016-12-30 17:29:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS NO RETURN SHOWN ON THE PLANS FOR BEDROOM #1
 ON THE FIRST FLOOR. M1602.4 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 2) REVISE THE EQUIPMENT SIZING CALCULATIONS FOR UNIT 2,
 USING THE EAST WALL WITH OPENINGS INSTEAD OF THE WEST
 WALL. FBC ENERGY CONSERVATION SECTION 405
  
 3) THE PLANS NEED TO SPECIFY THAT THE DOORS TO THE
 AIRHANDLER CLOSET ARE REQUIRED TO BE LOUVERED FOR
 RETURN AIR. FBC 107.2.1
  
 4) THE 10 " DIAMETER RETURN AIR TRANSFER DUCT SERVING
 THE MASTER BEDROOM IS NOT ADEQUATE FOR ALL OF THE
 SUPPLY AIR IN THE MASTER BEDROOM. IT APPEARS THAT A 14"
 DIAMETER WOULD BE REQUIRED. M1602.4 BALANCED RETURN
 AIR. EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE.
  
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (32 258
 MM2) (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR
 SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
  
  
  
  