Plan Review Notes For Permit 16111165 |
Permit Number |
16111165 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-01 09:30:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION IS DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE REVISION IS TO CHANGE THE HEATING AND COOLING | | EQUIPMENT FROM TRANE TO RHEEM. THE EQUIPMENT SCHEDULE | | CHANGED THE CONDENSER TO A RHEEM 13PJL60A01, HOWEVER | | THE COIL WAS NOT CHANGED FROM THE TRANE | | GAM2A0C60S51++TDR. THE AHRI REFERENCE NUMBER 5720554 IS | | NOT CORRECT. PER FBC ENERGY CONSERVATION R101.4.7 AND | | R403.6 MATCHED SYSTEMS ARE REQUIRED. | | | | |
|