Plan Review Notes
Plan Review Notes For Permit 16111164
Permit Number 16111164
Review Stop M
Sequence Number 3
Notes
Date Text
2017-01-03 19:06:05RESIDENTIAL (R3) THIRD MECHANICAL REVISION CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN
 REVIEW FEE. FLORIDA STATUTE 553.80(2)(B).
  
 ORIGINAL COMMENT:
 1- INFORMATION SHOWN ON SHEET M1.00 DOESN'T MATCH
 INFORMATION SHOWN ON THE AHRI CERTIFICATE # 9962635 AND
 #8205993 SPECIFIED ON THE EQUIPMENT SCHEDULE & LEGEND
 SUBMITTED. REVISE OUTDOOR UNIT MODEL NUMBER, SEER,
 COOLING CAPACITY, ETC. AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 THE AHRI CERTIFICATE NUMBER WAS CHANGED TO 7556872 AND
 7552655 RESPECTIVELY. UNABLE TO FIND THESE NUMBERS ON
 THE AHRI DIRECTORY. PLEASE PROVIDE COPIES OF THE
 REVISED AHRI CERTIFICATES.
 SEC. M1302.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]