2016-11-29 07:55:51 | 1ST REVIEW FBC-2014 RESIDENTIAL | | REVISION #16111107 | | MASTER #15100627 | | 11/29/16 | | | | 1) IDENTIFY ALL ROOMS AND SPACES ON THE LAYOUT PLAN- | | SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | 2) INDICATE THE TYPE AND SIZE OF DRYER EXHAUST DUCT, | | SHOW THE DUCT RUN AND TERMINATION LOCATION- M1502. | | | | 3) SHOW THE 2ND FLOOR BATH EXHAUST DUCT RUNS AND | | TERMINATION LOCATIONS- M1501.1 | | | | 4) THE 10X10 RETURN GRILLS ARE UNDERSIZED FOR 225 & 250 | | CFMS- SECTION M1602.4. 50 SQ. INCHES PER 100 CFM | | REQUIRED- | | | | 5) PROVIDE CONDENSER ANCHORING DETAILS- M1305.1.4.1 & | | M1401.4 | | | | 6) SUBMIT SPECS FOR THE RANGE HOOD- M1503 | | | | 7) SUBMIT A SUB-PERMIT APPLICATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|