2016-12-13 14:58:48PASS PROVISO
 1) REFER TO SECTION 504.3 CLEANOUT. EACH VERTICAL RISER
 SHALL BE
 PROVIDED WITH MEANS OF CLEANOUT. 2014 FBC (M)
 2) REFER TO SECTION 501.3.1 LOCATION OF EXHAUST OUTLETS
 # 2
 SHALL BE 10FT. FROM OPERABLE OPENINGS INTO BUILDING.
 2014 FBC (M)
  