Plan Review Notes For Permit 16110960 |
Permit Number |
16110960 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-13 14:58:48 | PASS PROVISO | | 1) REFER TO SECTION 504.3 CLEANOUT. EACH VERTICAL RISER | | SHALL BE | | PROVIDED WITH MEANS OF CLEANOUT. 2014 FBC (M) | | 2) REFER TO SECTION 501.3.1 LOCATION OF EXHAUST OUTLETS | | # 2 | | SHALL BE 10FT. FROM OPERABLE OPENINGS INTO BUILDING. | | 2014 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|