Date |
Text |
2017-02-03 06:30:16 | 1) SHT. CVR - THERE IS A NOTE ON THE PLAN THAT READS " |
| SEPARATE FACILITIES SHALL NOT BE REQUIRED IN BUSINESS |
| AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR AREA OF |
| 3000 SF OR LESS." WHAT CODE ARE YOU CITING THIS FROM |
| AND WHAT IS THE SPECIFIC CODE SECTION? I COULD NOT FIND |
| ANY SUCH EXCEPTION IN THE 2014 FBC. CLARIFY. |
| 2) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES |
| AND FEMALES IN THE NUMBER SPECIFIED IN 2014 |
| FBC-PLUMBING TABLE 403.1. |
| 3) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR |
| THE BREWERY VESSELS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) THE MINIMUM WIDTH OF THE HANDICAPPED ACCESSIBLE |
| TOILET ROOM SHALL BE 85 INCHES TO COMPLY WITH THE |
| REQUIRED CLEAR FLOOR SPACES FOR THE PLUMBING FIXTURES |
| PER 2014 FBC-ACCESS. SECS.305, 604.3, 2014 FBC-PLUMBING |
| SEC. 405.3.1. |
| 5) SHT. A-3 - DETAIL #3 SHOWS THE TOP OF THE LAVATORY |
| AT 40 INCHES ABOVE THE FINISH FLOOR AND ALSO 34 INCHES |
| ABOVE THE FINISH FLOOR. THE MAXIMUM HEIGHT SHALL BE 34 |
| INCHES TO THE TOP OF THE LAVATORY. |
| 6) SHT. P-2 - THE 2 INCH AAV/VENT FOR THE MOP SINK AND |
| FLOOR SINK SHALL BE LOCATED BETWEEN THE TWO FIXTURES. |
| 2014 FBC-PLUMBING SECS. 901.2, 901.2.1. |
| 7) SHTS. EQ-1, E-2, & P-2 SHOW THE DOOR TO THE |
| ACCESSIBLE TOILET SWINGING INTO THE CLEAR FLOOR SPACE |
| FOR THE LAVATORY. COMPLY WITH 2014 FBC-ACCESS. SEC. |
| 603.2.3. |
| 8) THE TRENCH DRAIN TRAP SHALL BE PROVIDED WITH A TRAP |
| PRIMER. 2014 FBC-PLUMBING SEC.1002.4. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |