2017-02-03 06:30:161) SHT. CVR - THERE IS A NOTE ON THE PLAN THAT READS "
 SEPARATE FACILITIES SHALL NOT BE REQUIRED IN BUSINESS
 AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR AREA OF
 3000 SF OR LESS." WHAT CODE ARE YOU CITING THIS FROM
 AND WHAT IS THE SPECIFIC CODE SECTION? I COULD NOT FIND
 ANY SUCH EXCEPTION IN THE 2014 FBC. CLARIFY.
 2) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES
 AND FEMALES IN THE NUMBER SPECIFIED IN 2014
 FBC-PLUMBING TABLE 403.1.
 3) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 THE BREWERY VESSELS. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE MINIMUM WIDTH OF THE HANDICAPPED ACCESSIBLE
 TOILET ROOM SHALL BE 85 INCHES TO COMPLY WITH THE
 REQUIRED CLEAR FLOOR SPACES FOR THE PLUMBING FIXTURES
 PER 2014 FBC-ACCESS. SECS.305, 604.3, 2014 FBC-PLUMBING
 SEC. 405.3.1.
 5) SHT. A-3 - DETAIL #3 SHOWS THE TOP OF THE LAVATORY
 AT 40 INCHES ABOVE THE FINISH FLOOR AND ALSO 34 INCHES
 ABOVE THE FINISH FLOOR. THE MAXIMUM HEIGHT SHALL BE 34
 INCHES TO THE TOP OF THE LAVATORY.
 6) SHT. P-2 - THE 2 INCH AAV/VENT FOR THE MOP SINK AND
 FLOOR SINK SHALL BE LOCATED BETWEEN THE TWO FIXTURES.
 2014 FBC-PLUMBING SECS. 901.2, 901.2.1.
 7) SHTS. EQ-1, E-2, & P-2 SHOW THE DOOR TO THE
 ACCESSIBLE TOILET SWINGING INTO THE CLEAR FLOOR SPACE
 FOR THE LAVATORY. COMPLY WITH 2014 FBC-ACCESS. SEC.
 603.2.3.
 8) THE TRENCH DRAIN TRAP SHALL BE PROVIDED WITH A TRAP
 PRIMER. 2014 FBC-PLUMBING SEC.1002.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW