2017-01-25 17:26:04 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #16110835 |
| 1/25/17 |
| |
| SOME OF THE COMMENTS FROM THE 1ST REVIEW STILL EXIST OR |
| HAVCE NOT BEEN ADDRESSED ENTIRELY. PLEASE NOTE THAT A |
| 4X PLAN REVIEW FEE MAY APPLY IF THE PLAN IS DISAPPROVED |
| A THRID TIME FOR THE SAME CODE VIOLATIONS- SECTION |
| 553.80 FLORIDA STATUTES. |
| |
| 1) THE PROJECT IS DEFINED AS A CHANGE OF OCCUPANCY IN |
| ACCORDANCE WITH SECTION 202 AND 506.1 FBC-14 EXISTING |
| BUILDING CODES,. PLEASE CORRECT THE LEVEL 2 ALTERATION |
| NOTE ON SHEET CVR, AND REFER TO CHAPETER 10 FOR ALL |
| COMPLIANCE INFORMATION. |
| |
| 2) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION |
| AND SUBMIT DOCUMENTATION OF COMPLIANCE. SEE SECTION |
| C401.2 FOR COMPLIANCE PATH INFORMATION. |
| |
| 3) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS: EXHAUST |
| VENTILATION IS REQUIRED FOR THE TOILET ROOM AND THE |
| KITCHEN- SEE TABLE 403.3 AND SHOW COMPLIANCE. |
| |
| 4) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS: THE |
| PLAN IS INDICATING NATURAL VENTILATION. PLEASE SEE |
| SECTION 402.2 AND PROVIDE A CALCULATION. |
| |
| 5) THE REVISED PLAN INDICATES AND EXISTING 5TON HEAT |
| PUMP. PLEASE SHOW THE DUCT LAYOUT PLAN INDICATING ALL |
| ALTERATIONS TO THE EXISTING SYSTEM. AS PREVIOUSLY NOTED |
| IN 1ST REVIEW COMMENT #5, MINIMUM HEAT IS REQUIRED FOR |
| THE BAR AREA. |
| |
| 6) PROVIDE AN EQUIPMENT SCHEDULE FOR ALL BREWERY TANKS |
| AND EQUIPMENT, AND SUBMIT MANUFACTURER;S SPECIFCATIONS |
| FOR ALL. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |