2017-01-25 10:25:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110835
 ADD: 1142 OKEECHOBEE RD.
 CONT: MASTER CONTRACTORS
 TEL: 561-248-5498
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2NDD REVIEW
 DATE: WED. JAN. 25/2017
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SHEET A1 OF 13 SHOWS THE BREWERY AND THE ADJACENT
 BEER DRINKING AREA WITH A HALF WALL UNDER COUNTER.
 PLEASE SHOW COMPLIANCE WITH:
  
 3A) SEMI-COMPLIED. SHEET A1 SHOWS A DIFFERENT LAYOUT
 THAN SHEET EQ-1. 2014 ACCESSIBILITY CODE 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 3B) SEMI-COMPLIED. SHEET A1 SHOWS A DIFFERENT LAYOUT
 THAN SHEET EQ-1. 2014 ACCESSIBILITY CODE 226.2
 DISPERSION. DINING SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES.
  
 3C) 2ND REQUEST THE ACCESSIBLE TABLE HEIGHTS ARE
 UNKNOWN. 2014 ACCESSIBILITY CODE. 902.3 HEIGHT. THE
 TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 3D) COMPLIED. COUNTER HEIGHT. 36 INCHES.
  
 4) 2ND REQUEST. SHEET A-1 INDICATES AN EXISTING 5 TON
 HEAT PUMP UNDER A DIFFERENT PERMIT. PLEASE PROVIDE THE
 PERMIT NUMBER FOR THE HEAT PUMP BEING INSTALLED IN THIS
 BAY, (BAY 12/13). THE CITY RECORDS ONLY SHOW A 5 TON
 HEAT PUMP BEING INSTALLED IN BAY # 6 UNDER PERMIT
 08060846.
  
  
 THE PLANS SHEET A-1 NOTE 2 INDICATES THE GARAGE DOORS
 ARE TO BE OPEN DURING BUSINESS HOURS FOR VENTILATION
 AND NOTE 3 INDICATES THERE IS TO BE NO MECHANICAL WORK.
 PLEASE PROVIDE HOW COMPLIANCE WITH
 1204.1 EQUIPMENT AND SYSTEMS FBC-B WILL BE COMPLIED
 WITH.
 2014 FBC-B 1204.1 EQUIPMENT AND SYSTEMS. INTERIOR
 SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE PROVIDED
 WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS CAPABLE OF
 MAINTAINING AN INDOOR TEMPERATURE OF NOT LESS THAN 68?F
 (20?C) AT A POINT 3 FEET (914 MM) ABOVE THE FLOOR ON
 THE DESIGN HEATING DAY.
  
 5) COMPLIED. PALM BEACH COUNTY IMPACT FEES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  