Plan Review Notes For Permit 16110835 |
Permit Number |
16110835 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-12 13:20:04 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1. THE PLANS INDICATE A BUSINESS OCCUPANCY IF THEY ARE | | SERVING BEER TO THE PUBLIC ITS GOING TO BE A A2 | | OCCUPANCY IF THEY ARE JUST BREWING BEER IT SHOULD BE AN | | F2. PER FBC 303.3-303.6 | | THE OCCUPANT LOAD SHOULD BE CALCULATED USING 15 NET FOR | | SEATING AREA AND 100 GROSS FOR BEER BREWING AREA PER | | FBC TABLE 1004.1.2 | | | | 2. THE COVER SHEET IN THE PLUMBING FIXTURE CALCULATIONS | | IT INDICATES 1 WC 1 LAV FOR MALE AND 1 WC 1 LAV FOR | | FEMALE THE PLAN ONLY SHOWS ONE FOR BOTH TWO ARE | | REQUIRED. PER FBC PL | | 403.2 SEPARATE FACILITIES. | | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE | | FACILITIES SHALL BE PROVIDED FOR EACH SEX. | | | | 3. SHT. P-2 THE TRENCH DRAIN IS NOT VENTED. FBC PL | | 901.2.1 | | | | 4. IF THIS IS NOT AN A2 A DRINKING FOUNTAIN IS | | REQUIRED. PER FBC PL TABLE 403.1 |
|