Plan Review Notes
Plan Review Notes For Permit 16110835
Permit Number 16110835
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-28 10:03:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLAN SHEETS DO NOT INDICATE CONSISTANT
 ORDER OR COUNT.
  
  
 PLEASE CORRECT.
  
  
  
 2) SHEET CVR & A 2 - THE OCCUPANCY LOAD CALCULATION
 INDICATES FOR BUSINESS @ 30/SQ FT PER THE FBC; HOWEVER,
 THE FFPC REQUIREMENT IS @ 15/SQ FT, LESS CONCENTRATED
 USE. THIS WOULD AFFECT YOUR PROPOSED OCCUPANCY LOAD.
  
 ADDITIONALLY, THIS WOULD ALSO AFFECT YOUR KITCHEN AREA
 LOAD.
  
 NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.3.1.3 OCCUPANT LOAD INCREASES.
 7.3.1.3.1 THE OCCUPANT LOAD IN ANY BUILDING OR PORTION
 THEREOF SHALL BE PERMITTED TO BE INCREASED FROM THE
 OCCUPANT LOAD ESTABLISHED FOR THE GIVEN USE IN
 ACCORDANCE WITH 7.3.1.2 WHERE ALL OTHER REQUIREMENTS OF
 THIS CODE ARE ALSO MET, BASED ON SUCH INCREASED
 OCCUPANT LOAD.
  
 ASSEMBLY -LESS CONCENTRATED USE 15/SQ FT/PERSON
  
 KITCHEN - 100/SQ FT/PERSON
  
 PLEASE CORRECT OR MODIFY YOUR OCCUPANCY LOAD
 CALCULATIONS FOR EACH AREA TO MORE ACCURATELY REFLECT
 PER THE FFPC.
  
  
  
  
 3) SHEET A 2 - THE PLAN INDICATES TWO EXITS; HOWEVER,
 THEY DO NOT MEET THE REQUIREMENTS OF NFPA 101, CHAPTER
 12, NEW ASSEMBLY OCCUPANCIES & CHAPTER 7, MEAN OF
 EGRESS.
  
 CHAPTER 12
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR
 FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH
 12.2.4.4.
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH SECTION 7.5.
  
 CHAPTER 7
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET.
  
 TWO EXITS ARE INDICATED; HOWEVER, THEY DO NOT MEET THE
 SEPARATION REQUIRMENT:
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO THAT EXITS ARE READILY ACCESSIBLE AT
 ALL TIMES.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED
 IN 7.5.1.3.3 THROUGH 7.5.1.3.5.
  
  
 PLEASE PROVIDE FOR THE REQUIRED EXIT SEPARATION.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  