2016-12-01 17:49:33JOB PERMIT NUMBER: 16110835
 JOB ADDRESS: 1142 OKEECHOBEE RD
 WEST PALM BEACH FLORIDA
 DATE: DECEMBER 1, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] SHOW NEW WIRE-WAY SIZE IN ACCORDANCE WITH NEC 376 &
 378. SHOW WIRE SIZE FROM METER TO WIRE-WAY. FBC 107
  
 2] AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 18'' OF THE TOP OF A SHOW WINDOW FOR EVERY 12'
 OR MAJOR PORTION THEREOF AREA MEASURED HORIZONTALLY.
 NEC 210.62 (IF EXISTING PLEASE INDICATE ON PLANS).
  
 3] EACH COMMERCIAL BUILDING AND COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE 20 AMP DEDICATED OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO PEDESTRIANS. NEC
 600.5 (IF EXISTING PLEASE INDICATE ON PLANS).
  
 4] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4) A NOTE
 WILL SUFFICE.
  
 5] OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL
 CLASSROOMS, CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH
 AND BREAK ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE
 ROOMS AND JANITORIAL CLOSETS, AND OTHER SPACES 300
 SQUARE FEET (28 M2) OR LESS ENCLOSED BY
 FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER. FBC-E SECTION
 C405.2.2.2.
  
 6] ELECTRICAL EQUIPMENT IN OTHER THAN DWELLING UNITS
 LIKELY TO REQUIRE SERVICED WHILE ENERGIZED SHALL BE
 FIELD MARKED (LABEL SHALL WITHSTAND ENVIORMENT
 INVOLVED) TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
 NEC 110.16 A NOTE WILL SUFFICE.
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER