2016-11-30 19:04:03 | JOB PERMIT NUMBER: 16110832 |
| JOB ADDRESS: 915 A 5TH ST |
| WEST PALM BEACH FLORIDA |
| DATE: NOVEMBER 30, 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| |
| 1] THE LOAD CALCULATIONS PROVIDED USING THE STANDARD |
| METHOD PER YOUR NUMBERS IS UNDERSIZED, PLEASE ADJUST OR |
| PROVIDE OPTIONAL METHOD FOR VERIFICATION. |
| |
| NEC 220.12, 7200 SQFT X 3VA = 21,600 - 3000VA = 18,600 |
| X 35% = 6510 + 3000VA = 9510 |
| NEC 220.53, W/H 3000VA X 3 = 9000 |
| NEC 220.54, DRYER 5000VA X 3 = 15000 |
| NEC 220.55, RANGE 8000VA X 3 = 14000 |
| NEC 220.50 & 51, AC VS HEAT 5000VA X 3 = 15000 |
| TOTAL DEMAND LOAD, 62510VA / 240V = 260.5 AMPS |
| |
| 2] PROVIDE INTERSYSTEM BONDING TERMINAL IN THE |
| GROUNDING DETAIL. NEC 250.94 |
| |
| 3] SHOW PROPER IDENTIFICATION ON EACH DISCONNECT, LABEL |
| UNIT # EACH SERVE. NEC 225.37 |
| |
| 4] CLARIFY WHY THERE IS ANOTHER PERMIT APPLICATION OPEN |
| FOR THE SAME SCOPE OF WORK ON THIS PROPERTY, ANY |
| QUESTIONS PLEASE CONTACT ME DIRECTLY. |
| |
| REVIEW FBC 2014 5TH ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 561-805-6713 |