Plan Review Notes For Permit 16110822 |
Permit Number |
16110822 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-01 13:39:00 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S | | | | 1] NEC 210.52(B)(1) 2 SMALL APPLIANCE CIRCUITS | | REQUIRED. | | 2] NEC 210.8(A)(6) GFCI PROTECTION REQUIRED IN | | KITCHENS. | | 3] SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | 314 & 315. | | 4] TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.12 |
|