Plan Review Notes For Permit 16110821 |
Permit Number |
16110821 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-29 08:57:25 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16110821 | | 11/29/16 | | | | 1) PROVIDE NOTES TO VERIFY THAT THE AC SYSTEM PROVIDING | | THE 10" SUPPLY DUCTS TO THE HOOD WILL BE LINKED FOR FAN | | SHUTDOWN IN THE EVENT OF FIRE ALARM. | | | | 2) SUBMIT THE FAN NOA'S AND SPECS FOR THE FIRE WRAP. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|