Plan Review Notes
Plan Review Notes For Permit 16110786
Permit Number 16110786
Review Stop B
Sequence Number 4
Notes
Date Text
2018-02-06 09:40:35 
 02/06/18
  
 NOTE: MISSING ONE SET OF DRAWINGS. ONE SET OF PLANS WAS
 SIGNED OUT ON MARCH 01/2017 BUT IT WAS NEVER RETURNED.
 NEED TO HAVE TWO COMPLETE SETS WITH THE REVISED
 INSERTED AND OLD PLANS REMOVED. REVIEW WILL BE RESUMED
 WHEN SECOND SET OF PLANS IS SUBMITTED. JG.
  
  
 PRELIMINARY REVIEW OF REVISED PLAN FROM ARCHITECT DAVID
 LAWRENCE.
  
 1- IT LOOKS LIKE THE REVISED PLAN COMPLIES WITH THE
 WINDOW FALL PROTECTION AND SAFETY GLASS REQUIREMENTS.
 NEED TO REVISE WINDOW SCHEDULE ACCORDINGLY.
  
  
  
 RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION.
  
 1- REVISED UPPER LIVING ROOM WINDOWS AND REVISED
 WINDOWS FOR BEDROOM #210 LOCATED ON THE NORTH EAST
 CORNER NEED TO COMPLY WITH THE WINDOW FALL PROTECTION
 REQUIREMENTS OF SEC. R312.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE FALL
 PROTECTION.
 NOTE: THIS ALSO APPLIES TO THE MASTER BEDROOM WINDOWS
 AND ANY OTHER WINDOW WHERE THE BOTTOM OF THE WINDOW
 SILL IS LESS THAN 24" ABOVE FINISHED FLOOR AND MORE
 THAN 72" ABOVE FINISHED GRADE OR SURFACE BELOW.
 RESPONSE: SHEET A101 WAS REVISED SHOWING GUARDRAILS FOR
 ALL FOUR FIXED WINDOWS IN THE HALL BY THE MORNING
 BREAKFAST AREA, HALL 205 AND BEDROOM 210. THE GUARDRAIL
 WILL TAKE CARE OF THE SAFETY GLASS REQUIREMENTS. THESE
 FOUR DOORS ARE FIXED. THEY DON'T NEED TO COMPLY WITH
 THE WINDOW FALL PROTECTION. THE WINDOW FALL PROTECTION
 APPLIES TO THE WINDOWS ON BEDROOM 210 THAT ARE FACING
 EAST, THE WINDOWS ON MASTER TERRACE 214 AND THE WINDOWS
 ON MASTER BEDROOM THAT ARE FACING EAST. REVISE PLANS
 SHOWING COMPLIANCE WITH THE FALL PROTECTION FOR THOSE
 WINDOWS FOR ALL THE WINDOWS WHERE THE BOTTOM OF THE
 WINDOW SILL IS LESS THAN 24" ABOVE FINISHED FLOOR AND
 MORE THAN 72" ABOVE FINISHED GRADE OR SURFACE BELOW.
  
 2- SIX DRAWINGS WERE REVISED AND RE-SUBMITTED. OWES
 $309.00 FOR REVISION RE-SUBMITTAL FEES.
  
  
 REMAINDER: (NOT ADDRESSED AS OF 02/06/17)
 BUILDING REVIEW WAS APPROVED ON 05/13/16 WITH PROVISO.
 PROVISO ITEMS NEED TO BE SUBMITTED BEFORE INSPECTIONS
 TO AVOID DELAYS/CONFLICTS. SEE COPY OF COMMENTS BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- ENERGY CALCULATIONS SUBMITTED: REVISE ROOF FINISH
 MATERIAL INFORMATION ON PAGE 2 TO MATCH PLANS.
 2- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR ALL
 FIREPLACES SHOWN ON PLANS. NOTE: DESIGNER OF RECORD TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY
 NOTE #8 ON PAGE 2 OF 76.
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A)ENTRY DOOR AS SPECIFIED ON PLANS. DRAWING NO
 "LAG-TEN" SUBMITTED DON'T CORRESPOND TO FLORIDA PRODUCT
 APPROVAL COVER PAGE FL15911-R1 SUBMITTED.
 B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES, GARAGE
 SWING DOOR, LAUNDRY ROOM, CABANA BATHROOM AND CABANA
 STORAGE.
 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]