Plan Review Notes For Permit 16110786 |
Permit Number |
16110786 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-02-07 12:37:40 | 3RD REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: 3RD REQUEST | | | | 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | NEW COMMENT: | | | | 1. TWO SETS OF PLANS ARE REQUIRED. PER WPB AMEND TO FBC | | 107.2 |
|