2017-02-06 12:48:22 | RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION. |
| |
| 1- REVISED UPPER LIVING ROOM WINDOWS AND REVISED |
| WINDOWS FOR BEDROOM #210 LOCATED ON THE NORTH EAST |
| CORNER NEED TO COMPLY WITH THE WINDOW FALL PROTECTION |
| REQUIREMENTS OF SEC. R312.2 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE FALL |
| PROTECTION. |
| NOTE: THIS ALSO APPLIES TO THE MASTER BEDROOM WINDOWS |
| AND ANY OTHER WINDOW WHERE THE BOTTOM OF THE WINDOW |
| SILL IS LESS THAN 24" ABOVE FINISHED FLOOR AND MORE |
| THAN 72" ABOVE FINISHED GRADE OR SURFACE BELOW. |
| RESPONSE: SHEET A101 WAS REVISED SHOWING GUARDRAILS FOR |
| ALL FOUR FIXED WINDOWS IN THE HALL BY THE MORNING |
| BREAKFAST AREA, HALL 205 AND BEDROOM 210. THE GUARDRAIL |
| WILL TAKE CARE OF THE SAFETY GLASS REQUIREMENTS. THESE |
| FOUR DOORS ARE FIXED. THEY DON'T NEED TO COMPLY WITH |
| THE WINDOW FALL PROTECTION. THE WINDOW FALL PROTECTION |
| APPLIES TO THE WINDOWS ON BEDROOM 210 THAT ARE FACING |
| EAST, THE WINDOWS ON MASTER TERRACE 214 AND THE WINDOWS |
| ON MASTER BEDROOM THAT ARE FACING EAST. REVISE PLANS |
| SHOWING COMPLIANCE WITH THE FALL PROTECTION FOR THOSE |
| WINDOWS FOR ALL THE WINDOWS WHERE THE BOTTOM OF THE |
| WINDOW SILL IS LESS THAN 24" ABOVE FINISHED FLOOR AND |
| MORE THAN 72" ABOVE FINISHED GRADE OR SURFACE BELOW. |
| |
| 2- SIX DRAWINGS WERE REVISED AND RE-SUBMITTED. OWES |
| $309.00 FOR REVISION RE-SUBMITTAL FEES. |
| |
| |
| REMAINDER: (NOT ADDRESSED AS OF 02/06/17) |
| BUILDING REVIEW WAS APPROVED ON 05/13/16 WITH PROVISO. |
| PROVISO ITEMS NEED TO BE SUBMITTED BEFORE INSPECTIONS |
| TO AVOID DELAYS/CONFLICTS. SEE COPY OF COMMENTS BELOW: |
| |
| BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- ENERGY CALCULATIONS SUBMITTED: REVISE ROOF FINISH |
| MATERIAL INFORMATION ON PAGE 2 TO MATCH PLANS. |
| 2- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR ALL |
| FIREPLACES SHOWN ON PLANS. NOTE: DESIGNER OF RECORD TO |
| REVIEW/APPROVE PRIOR TO SUBMITTAL. |
| 3- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5 |
| SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY |
| NOTE #8 ON PAGE 2 OF 76. |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A)ENTRY DOOR AS SPECIFIED ON PLANS. DRAWING NO |
| "LAG-TEN" SUBMITTED DON'T CORRESPOND TO FLORIDA PRODUCT |
| APPROVAL COVER PAGE FL15911-R1 SUBMITTED. |
| B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES, GARAGE |
| SWING DOOR, LAUNDRY ROOM, CABANA BATHROOM AND CABANA |
| STORAGE. |
| 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS. |
| |