Plan Review Notes
Plan Review Notes For Permit 16110786
Permit Number 16110786
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-20 12:31:45PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A SUMMARY LOAD CALCULATION FOR THE SELECTION
 AND SIZING OF THE ELECTRICAL SERVICE AS NOTED WITHIN
 THE NEC. CONTINUOUS LOADS SUCH AS AC SHOULD BE INCLUDED
 AT 100%. NEC 220.4, 220.80
  
 INTERCONNECTED SMOKE ALARMS ARE REQUIRED BOTH WITHIN
 AND OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 THE ELECTRIC SUBPANEL AT THE GUEST HOUSE MAY NOT BE
 LOCATED IN A CLOSET. PANELS SHALL BE PLACED SO AS TO
 REDUCE TO A MINIMUM THE PROBABILITY OF COMMUNICATING
 FIRE TO ADJACENT COMBUSTIBLE MATERIALS. OVERCURRENT
 DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY
 IGNITABLE MATERIAL. SUFFICIENT ACCESS AND WORKING SPACE
 IS REQUIRED AT THE SUB PANEL. 36"X 30? IN WIDTH IS THE
 MINIMUM REQUIRED FOR SUB PANELS. NEC 408.17, 240.24
 (D), 110.26 (A)
  
 CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE
 LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT. NEC 410.116;
 FBC R 4004
  
 SWIMMING POOL PUMPS AND SPA EQUIPMENT MUST BE GFCI
 PROTECTED. NEC 680.21(C), FBC R E4203.1.3
  
 PROVIDE SAFE WORKING CLEARANCES FOR ALL OUTSIDE AIR
 CONDITIONING UNIT DISCONNECTS. NEC 110.26, FBC E3405.1
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6754(OFFICE)
 561-373-3701(CELL)
  