2016-12-20 12:31:45 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| PROVIDE A SUMMARY LOAD CALCULATION FOR THE SELECTION |
| AND SIZING OF THE ELECTRICAL SERVICE AS NOTED WITHIN |
| THE NEC. CONTINUOUS LOADS SUCH AS AC SHOULD BE INCLUDED |
| AT 100%. NEC 220.4, 220.80 |
| |
| INTERCONNECTED SMOKE ALARMS ARE REQUIRED BOTH WITHIN |
| AND OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| |
| THE ELECTRIC SUBPANEL AT THE GUEST HOUSE MAY NOT BE |
| LOCATED IN A CLOSET. PANELS SHALL BE PLACED SO AS TO |
| REDUCE TO A MINIMUM THE PROBABILITY OF COMMUNICATING |
| FIRE TO ADJACENT COMBUSTIBLE MATERIALS. OVERCURRENT |
| DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY |
| IGNITABLE MATERIAL. SUFFICIENT ACCESS AND WORKING SPACE |
| IS REQUIRED AT THE SUB PANEL. 36"X 30? IN WIDTH IS THE |
| MINIMUM REQUIRED FOR SUB PANELS. NEC 408.17, 240.24 |
| (D), 110.26 (A) |
| |
| CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE |
| LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9 |
| |
| HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| NEED TO BE RATED FOR INSULATION CONTACT. NEC 410.116; |
| FBC R 4004 |
| |
| SWIMMING POOL PUMPS AND SPA EQUIPMENT MUST BE GFCI |
| PROTECTED. NEC 680.21(C), FBC R E4203.1.3 |
| |
| PROVIDE SAFE WORKING CLEARANCES FOR ALL OUTSIDE AIR |
| CONDITIONING UNIT DISCONNECTS. NEC 110.26, FBC E3405.1 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94; FBC R E3609 |
| |