Plan Review Notes
Plan Review Notes For Permit 16110764
Permit Number 16110764
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-28 09:14:581ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 1] A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS
 SHALL BE PROVIDED TO SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS LOCATED IN THE KITCHEN. NEC
 210.52(B)(1) A NOTE WILL SUFFICE.
  
 2] SHOW GFCI PROTECTED RECEPTACLE OUTLETS & COMPLY WITH
 COUNTER TOP SPACING REQUIREMENTS ON THE KITCHEN LAYOUT
 FLOOR PLAN, INCLUDE ALL KITCHEN APPLIANCES OUTLET
 LOCATION (RANGE,DISHWASHER,MICROWAVE, & ETC) ASWELL PER
 NEC 210.8(A)(6) & 210.52(C)
  
  