Plan Review Notes For Permit 16110764 |
Permit Number |
16110764 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-28 09:14:58 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | | | 1] A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS | | SHALL BE PROVIDED TO SERVE ALL WALL AND FLOOR | | RECEPTACLE OUTLETS LOCATED IN THE KITCHEN. NEC | | 210.52(B)(1) A NOTE WILL SUFFICE. | | | | 2] SHOW GFCI PROTECTED RECEPTACLE OUTLETS & COMPLY WITH | | COUNTER TOP SPACING REQUIREMENTS ON THE KITCHEN LAYOUT | | FLOOR PLAN, INCLUDE ALL KITCHEN APPLIANCES OUTLET | | LOCATION (RANGE,DISHWASHER,MICROWAVE, & ETC) ASWELL PER | | NEC 210.8(A)(6) & 210.52(C) | | | | |
|