2016-11-30 10:45:45 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] VERIFY GEC SIZE WITH TABLE NEC 250.66 BASED ON THE | | LARGEST SERVICE UNGROUNDED CONDUCTOR. | | | | 2] CLARIFY IF ATS EQUIPMENT IS SERVICE RATED ? NEC | | 230.66 | | | | 3] IS THE PROPOSED GENERATOR A SEPERATELY OR | | NON-SEPERATETLY DERIVED SYSTEM, IF CALLED OUT AS | | NON-SEPERATELY PLEASE SHOW AN EQUIPMENT GROUNDING | | CONDUCTOR TO THE GENERATOR ON THE RISER DIAGRAM. NEC | | 250.35 |
|