Plan Review Notes For Permit 16110641 |
Permit Number |
16110641 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-17 13:55:57 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] ALONG WITH THE RISER DIAGRAM PROVIDE COMPLETE LOAD | | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | FLOOR PLAN. FBC 107.3.5.3 | | | | 2] PLEASE ADD THE INTERSYSTEM BONDING TERMINAL TO THE | | GROUNDING DETAIL REQUIRED PER FBC-R SECTION E3609.3 | | | | 3] PROVIDE AN ELECTRICAL SITE SPECIFIC FLOOR PLAN WITH | | ALL POWER & LIGHTING OUTLETS AND INCLUDE THE FOLLOWING; | | | | A] 2 SMALL APPLIANCE DEDICATED 20 AMP CIRCUITS IN THE | | KITCHEN GFCI PROTECTED. FBC-R SECTION E3703.2 & E3902.6 | | B] LOCATION OF SMOKE DETECTORS ON THE FLOOR PLAN. FBC-R | | SECTION 314 & 315 | | C] MARK AFCI PROTECTED CIRCUITS ON THE FLOOR PLAN. . | | FBC-R SECTION E3902.12 | | D] ADD A NOTE FOR TAMPER-RESISTANT RECEPTACLES. FBC-R | | SECTION E4002.14 | | E] SHOW THE SERVICE RECEPTACLE BY THE MECHANICAL | | EQUIPMENT. FBC-R SECTION E3901.11 |
|