Plan Review Notes For Permit 16110616 |
Permit Number |
16110616 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-17 10:25:45 | JOB PERMIT NUMBER: 16110616 | | JOB ADDRESS: 5001 N MILITARY TRAIL | | WEST PALM BEACH FLORIDA (THE BALLPARK OF THE PALM | | BEACHES) | | DATE: NOVEMBER 17, 2016 | | ELECTRICAL PLAN REVIEW COMMENTS | | | | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA | | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH | | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. | | | | 1] CLARIFY ILLUMINATION LEVELS BEING LESS THAN 1' | | CANDLE IN THE FOLLOWING AREAS; WEST APPROACH ROAD, EAST | | APPROACH ROAD, & SOUTH PROPERTY LINE. REFER TO | | FBC-1006.2 | | | | 2] PROVIDE A VOLTAGE DROP SCHEDULE TO COMPLY WITH FBC-E | | SECTION C405.7.3.2 BRANCH CIRCUIT CONDUCTORS SHALL BE | | SIZED FOR A MAXIMUM VOLTAGE DROP OF 3% DESIGN LOAD. | | PLEASE INCLUDE WIRE & CONDUIT SIZE ON THE SCHEDULE | | CHART. | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER | | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES | | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER | | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME | | DIRECTLY. | | | | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | |
|