Plan Review Notes
Plan Review Notes For Permit 16110575
Permit Number 16110575
Review Stop P
Sequence Number 2
Notes
Date Text
2017-04-28 15:15:262ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH.
  
 2ND REQUEST 2) SHT. F-2 - THE HOSE BIBB SHALL BE
 EQUIPPED WITH A SHUTOFF VALVE AND A VACUUM BREAKER.
 2014 FBC SEC.606.2, 608.15.4.
 2ND REQUEST 3) INDICATE ON THE PLANS WHERE THE FLOOR
 DRAIN IN THE PUMP ROOM DISCHARGES. THE FLOOR DRAIN
 SHALL DISCHARGE TO THE SANITARY AND BE EQUIPPED WITH A
 TRAP PRIMER.2014 FBC SEC.1002.4. SUBMNIT SANITARY RISER
 DIAGRAM AND ALSO A WATER RISER DIAGRAM FOR ANY AND ALL
 DOMESTIC WATER PIPING AND SANITARY DRAIN PIPING FOR
 THIS PROJECT. WPB AMEND. TO FBC SEC. 107.2.1.
  
 2ND REQUEST 5) SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE AQUASTAR CHANNEL DRAIN. WPB AMEND. TO 2014 FBC SEC.
 107.2.1.
 2ND REQUEST 6) THE AUTO FILL SHALL BE EQUIPPED WITH AN
 APPROVED BACKFLOW PREVENTION DEVICE. 2014 FBC-
 PLUMBING, SEC. 608.13, 608.15.
 2ND REQUEST 7) SHT. F-4 - PLACE A NOTE / DETAILS ON THE
 PLANS AS TO HOW THE PIPE SUPPORTS WILL BE SECURED TO
 THE SUBSTRATE AND THE SPACING OF SAID SUPPORTS. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  